GIS Surge Arrester
Product introduction:
This kind of surge arrester is used in SF6 gas-insulated swtichgear.
Advantage:
1/ Low partial discharge and Low residual voltage;
2/ High mechnical strength, good sealing.
3/ High dielectric insulation level;
4/ Tolerance to high/low temperature;
5/ Explosion-proof;
7/ Top lead-out, side lead-out. bottom lead-out. etc;
8/ Optimized structure, easy installation and reliable quality.
Standard Technical Data:
Below info. only for your reference, all data shall be specified and determined by technical specification and customer demand.
Item | Type | System nominal voltage | Rated voltage | COV | Nominal discharge current kA (peak) | Reference voltage at 1mA DC current | Residual voltage under lightning impulse | Residual voltage under steeping impulse | Residual voltage under switching impulse | High current impulse withstand 4/10μS (peak) | 2ms Square wave impulse withst and current (peak) |
1 | YH10WF-90/235 | 66 | 90 | 72.5 | 10 | 130 | 235 | 264 | 201 | 100 | 800 |
2 | YH10WF-96/250 | 110 | 96 | 75 | 10 | 140 | 250 | 280 | 213 | 100 | 800 |
3 | YH10WF-100/260 | 110 | 100 | 78 | 10 | 145 | 260 | 291 | 221 | 100 | 800 |
4 | YH10WF-102/266 | 110 | 102 | 79.6 | 10 | 148 | 266 | 297 | 226 | 100 | 800 |
5 | YH10WF-108/281 | 110 | 108 | 84 | 10 | 157 | 281 | 315 | 239 | 100 | 800 |
Schematic diagram:
Reference:
1/ Shendian MOA is widely used in China EHV (Extra hight voltage) projects of State Grid, Southern Power Grid.
2/ Supplied MOA to ABB/Siemens/Schneider more than 20 years, as well as other capacitor/switchgear manufacturers.
3/ Shendian MOA has been exported to more than 30 counties all over the world.