Add to Cart
20kV Combination Type 3P Surge Arrester For Substation
Product introduction:
Combined polymer metal-oxide surge arrester has been widely used for interphase protection and phase protection in the industry of petrochemical, railway and coal industry, etc.
Item | Description | Offered | Offered | |
1 | Manufacture/ Country of Origin | Xi'an Shendian/ China | Xi'an Shendian/ China | |
2 | Model | YH5WZ1-30/80×30/80 | YH5WZ1-34/89×34/89 | |
3 | Applicable standard | IEC 60099-4 | IEC 60099-4 | |
4 | Type | Outdoor, ZnO, gapless | Outdoor, ZnO, gapless | |
5 | Norminal voltage of system | kV | 20 | 20 |
6 | Earthing system | Effectively earthed | Effectively earthed | |
7 | Rated frequency | Hz | 50/60 | 50/60 |
8 | Rated voltage of SA | kV | 30 | 34 |
9 | Maximum continuous operating voltage | kV | 24 | 27.2 |
10 | Connection mode | Phase-Phase/ Phase-Earth | Phase-Phase/ Phase-Earth | |
11 | Power frequency reference voltage | kV | 45.0/43.0 | 50.0/48.0 |
12 | at reference current of | mA (D.C) | 1 | 1 |
Note: State peak value or rms. | ||||
13 | Nominal discharge current | kA | 5 | 5 |
14 | (a) Lightning impulse | kV | ≤80/80 | ≤89/89 |
(b) Steeping impulse | kV | ≤92/92 | ≤102/102 | |
(c) Switching impulse | kV | ≤68/68 | ≤75.6/75.6 |
Schematic diagram: